AC RCD (Residual Current Device), 1P+N (2 Pole) (NO), AC-3/AC-3e, < = 440V
EKL6-100(H)series Residual current circuit breakers withoutover current protection range provide a protection to both the persons and the electrical appliances, as they are designed to automatically cutoff the power supply in case of earth leakage.
They can be used as protection devices for 240V single-phase network.
Its maximum rated current reaches 100A, and the minimum leakage current has 4 options: 10mA, 30mA, 100mA, and 300mA.
The RCD is equipped with an indication window and a reset button to distinguish between residual current trips (reset button pops up).
- Certificate: CE;
- Electric ratings: AC 50/60HZ, 240V;
- Application:
For protection against risk of fire due to live to earth fault where fault current is insufficient to cause over current protection device to operate.
For protection against risk of shock from indirect contact with equipment suffering a live to earth fault.
For protection against shock in potentially hazardous environment .
As supplementary protection against shock from directly touching "Live" parts.
Note:an RCD must not be used as the sole means of protection against touching live parts
- Altitude: ≦ 2000m;
- Ambient temperature: -5℃ ~ +40 ℃;
- Mounting category: Ⅲ;
- Mounting conditions: Inclination between the mounting plane andthe vertical plane should not exceed ± 5°;
- Standard: GB/T16916.1, IEC61008-1;GB/T22794, IEC62423 (B type)
- 2 Years warranty
Model Number |
EKL6-100(H) |
||||
Electrical Features |
Mode |
Electromagnetic |
|||
Type |
AC; A; G, S; B |
||||
Rated current In |
16, 25, 32, 40, 63, 80, 100A |
||||
Poles |
1P+N (2P) |
||||
Rated voltage Ue |
2P 240V~ |
||||
Insulation voltage Ui |
500V |
||||
Rated frequency |
50/60Hz |
||||
Rated residual operating current (I△n) |
10, 30, 100, 300mA (AC; A; S type); 30, 100, 300mA (B type); |
||||
Rated residual making and breaking capacity (I△m) |
500A(In≤40A),10In(In>40A) |
||||
Short-circuit current Inc= I△C |
6,000A/10,000A |
||||
SCPD fuse |
|
||||
Break time under (I△n) |
≤0.1s (S type ≤ 0.5s) |
||||
Energy limiting class |
3 |
||||
Rated impulse withstand voltage(1.5/50)Uimp |
4,000V |
||||
Dielectric test voltage at ind.Freg.for 1min |
2.5kV |
||||
Pollution degree |
2 |
||||
Thermo-magnetic release characteristic B :(3-5) x In, C:(5-10) x In, D :(10-20) x In |
B, C, D (AC; A; S type); B, C (B type); |
||||
Mechanical Features |
Electrical life |
2,000 Cycles |
|||
Mechanical life |
4,000 Cycles |
||||
Contact position indicator |
Yes |
||||
Protection degree |
IP 20 |
||||
Reference temperature for setting of thermal element |
30°C |
||||
Ambient temperature (with daily average ≤35°C) |
-5°C~+40°C |
||||
Storage temperature |
-25°C~+70°C |
||||
Installation |
Terminal connection type |
Cable/ Pin-type busbar / U-type busbar |
|||
Terminal size top/bottom for cable |
35mm2; 18-2AWG |
||||
Terminal size top/bottom for busbar |
35mm2; 18-2AWG |
||||
Tightening torque |
3Nm 22In-lbs |
||||
Mounting |
On DIN rail EN60715(35mm) by means of fast clip device |
||||
Connection |
Power supply in both directions |
||||
Tripping Current Range |
Type |
Tripping current I△/A |
|||
AC |
0.5I△n<I△<I△n |
||||
A |
Lagging Angle |
I△n>0.01A |
I△n≤0.01A |
||
0° |
0.35I△n≤I△n≤1.4I△n |
0.35I△n≤I△n≤2I△n |
|||
90° |
0.25I△n≤I△n≤1.4I△n |
0.25I△n≤I△n≤2I△n |
|||
135° |
0.11I△n≤I△n≤1.4I△n |
0.11I△n≤I△n≤2I△n |
|||
Packing information |
Net weight (Kg) |
0.18 |
|||
Product dimensions (H*W*D)(mm) |
83*36*78 |
||||
Qty / Carton (pcs) |
100 |
||||
G.W. / Carton (Kg) |
19 |