AC RCBO (Residual Current Circuit Breaker with Overload Protection), 1P+N (2 Pole) (NO), AC-3/AC-3e, < = 440V

EKL9-40 series Residual current circuit breakers with over current protection range provide a full protection to both the persons and the electrical appliances, as they are designed to automatically cutoff the power supply in case of overload, short-circuit and earth leakage.

They can be used as protection devices for 240V single-phase network.

Its maximum rated current reaches 40A, and the minimum leakage current has 4 options: 10mA, 30mA, 100mA, and 300mA.

The RCBO is equipped with an indication window and a reset button to distinguish between residual current trips (reset button pops up) and overload trips (indication window turns red).

The RCBO is in three or five DIN modules, so it is easier to install than the common solution MCB + add-on blocks.

Share

Related products

No data

 
 

- Certificate: CE;

- Electric ratings: AC 50/60HZ, 240V;

- Application:

Type AC: They are commonly installed in homes and meant to be used for alternating sinusoidal residual current to offer inductive, capacitive, or resistive equipment. These RCBOs operate instantaneously to detect imbalance and do not have a time delay.

Type A: Are used for residual pulsating DC of up to 6mA and alternating sinusoidal residual current

Type B: They are used for three and single-phase equipment such as escalators, lifts, photovoltaic systems, welding equipment, and inverters.

- Altitude: ≦ 2000m;

- Ambient temperature: -5℃ ~ +40 ℃;

- Mounting category: Ⅲ;

- Mounting conditions: Inclination between the mounting plane andthe vertical plane should not exceed ± 5°;

- Standard: GB/T16917.1, IEC/EN 61009-1;GB/T22794, IEC62423 (B type)

- 2 Years warranty

Model Number

EKL9-40

Electrical Features

Mode

Electronic

Type

AC; A

Rated current In

6, 8, 10, 13, 16, 20, 25, 32, 40A

Poles

1P+N (2P)

Rated voltage Ue

2P 240V~

Insulation voltage Ui

500V

Rated frequency

50/60Hz

Rated residual operating current (I△n)

10, 30, 100, 300mA

Break time under (I△n)

≤0.1s (S type ≤ 0.5s)

Rated breaking capacity

6,000A

Energy limiting class

3

Rated impulse withstand voltage(1.5/50)Uimp

4,000V

Dielectric test voltage at ind.Freg.for 1min

2kV

Pollution degree

2

Thermo-magnetic release characteristic

B :(3-5) x In, C:(5-10) x In, D :(10-20) x In

B, C

Mechanical Features

Electrical life

4,000 Cycles

Mechanical life

10,000 Cycles

Contact position indicator

Yes

Protection degree

IP 20

Reference temperature for setting of thermal element

30°C

Ambient temperature (with daily average ≤35°C)

-5°C~+40°C

Storage temperature

-25°C~+70°C

Installation

Terminal connection type

Cable/ Pin-type busbar / U-type busbar

Terminal size top/bottom for cable

16mm2; 18-5AWG

Terminal size top/bottom for busbar

16mm2; 18-5AWG

Tightening torque

2.5Nm 22In-lbs

Mounting

On DIN rail EN60715(35mm) by means of fast clip device

Connection

From top

Combination with accessories

Auxiliary contact

EKM2-OF

Alarm contact

EKM2-FB

Shunt release

EKM2-MX

Over voltage protection

Yes

Under voltage protection

Yes

Over/Under voltage protection

Yes

Packing information

Net weight (Kg)

0.09

Product dimensions (H*W*D)(mm)

83*18*73

Qty / Carton (pcs)

200

G.W. / Carton (Kg)

19

  • TOP